Ture Online UPS
|
|
AC input
|
|
|
Phase
|
Three-phase three-wire
|
Single phase L+N
|
Voltage
|
380¡À15%VAC
|
220¡À15%VAC
|
Frequency Range
|
50¡À5% Hz
|
50¡À5% Hz
|
Power factor
|
¡Ý0.9 (linear full load)
|
¡Ý0.7(linear full load)
|
AC output
|
|
|
Rated Capacity
|
8/10/15/25/30 KVA
|
3/5/8/10 KVA
|
Rated voltage
|
Single phase 220VAC
|
Single phase 220VAC
|
Voltage accuracy
|
220¡À3%VAC
|
220¡À3%VAC
|
Output frequency
|
50¡À0.2Hz (battery status)
|
50¡À0.2Hz (battery status)
|
Power factor
|
0.8
|
0.8
|
Wave crest coefficient
|
3:01:00
|
3:01:00
|
Output waveform
|
Pure sine wave
|
Pure sine wave
|
Waveform distortion
|
<3% (linear full load)
|
<3% (linear full load)
|
Overload capacity
|
105%~125%, standby for 10 minutes and then transfer to bypass;
125%~150%, standby for 1 minute and then transfer to bypass;
150% transfer to bypass immediately. and automatically return to UPS mode after the overload is eliminated
|
105%~125%, standby for 10 minutes and then transfer to bypass;
125%~150%, standby for 1 minute and then transfer to bypass;
150% transfer to bypass immediately. and automatically return to UPS mode after the overload is eliminated
|
Current unbalance when parallel
|
¡Ü5%
|
¡Ü5%
|
Switching time
|
<4ms
|
<4ms
|
Efficiency
|
AC/AC>82 %; DC/AC>87%
|
AC/AC>82 %; DC/AC>87%
|
DC input
|
|
|
Voltage
|
220VDC / 110VDC
|
220VDC / 110VDC
|
Voltage range (undervoltage point can be set)
|
220VDC: 198VDC (default)-260VDC
110VDC: 95(default)-150VDC
|
220VDC: 198VDC (default)-260VDC
110VDC: 95(default)-150VDC
|
Over heat protection
|
15-30KVA: 85¡æ, 3-10KVA:75¡æ, transfer to bypass input
|
15-30KVA: 85¡æ, 3-10KVA:75¡æ, transfer to bypass input
|
Short circuit protection
|
Automatically current limitation, UPS shut down, the circuit breaker will trip
|
Automatically current limitation, UPS shut down, the circuit breaker will trip
|
Over voltage alarm
|
Over voltage alarm
|
Over voltage alarm
|
Under voltage alarm and protection
|
Undervoltage alarm, battery under voltage, UPS shuts down, and transfers to bypass
|
Undervoltage alarm, battery under voltage, UPS shuts down, and transfers to bypass
|
Display
|
|
|
LED indication
|
AC input light, inverter light, bypass light, battery light, overload light, fault light
|
AC input light, inverter light, bypass light, battery light, overload light, fault light
|
LCD display
|
Bypass, AC input, AC output, battery voltage; frequency; power factor, load percentage; UPS working status, etc.
|
Bypass, AC input, AC output, battery voltage; frequency; power factor, load percentage; UPS working status, etc.
|
Alarm
|
|
|
Buzzer
|
AC input off, battery under voltage, output overload, UPS fault, etc.
|
AC input off, battery under voltage, output overload, UPS fault, etc.
|
Communication
|
|
|
RS485 interface
|
Two RS485 channel, modbus protocol.
|
Two RS485 channel, modbus protocol.
|
Environment parameter
|
|
|
Operation temperature
|
-10~40¡æ
|
-10~40¡æ
|
Humidity
|
<95% (non-condensing)
|
<95% (non-condensing)
|
Noise
|
<65dB (one meter distance)
|
<65dB (one meter distance)
|
Size/Weight
|
|
|
Dimensions(mm)W¡ÁD¡ÁH
|
3KVA:
420x460x267£¨110VDC transformer inside£©60KGS
440x450x177£¨220VDC transformer inside£©55KGS
440x450x132£¨transformer outside£©12KGS
5KVA:
420x460x352£¨transformer inside£©85KGS
440x450x132£¨transformer outside£©12KGS
8/10/15/20/30KVA£º
440x450x132£¨transformer outside£©14-16KGS
|
3KVA:
420x460x267£¨110VDC transformer inside£©60KGS
440x450x177£¨220VDC transformer inside£©55KGS
440x450x132£¨transformer outside£©12KGS
5KVA:
420x460x352£¨transformer inside£©85KGS
440x450x132£¨transformer outside£©12KGS
8/10/15/20/30KVA£º
440x450x132£¨transformer outside£©14-16KGS
|